SSU31/AC400V
- 1 changeover contact
- Contact material AgNi
- Pluggable
- Monitoring: phase sequence, phase failure, undervoltage
- Contact material AgNi
- Pluggable
- Monitoring: phase sequence, phase failure, undervoltage
ELDAS®:
543730450
| Current type | AC (50 Hz) |
|---|---|
| Nominal voltage | 400 V |
| Housing material | PC |
|---|---|
| Ingress Protection | IP 20 |
| Operation temperature | -25 … 60 °C |
| Storage temperature (no ice) | -40 … 85 °C |
| Weight | 300 g |
| Overvoltage category | III |
|---|---|
| Pollution degree | 2 |
| Rated test voltage measuring / measuring circuit | 2 kV rms / 1 min |
| Rated test voltage measuring circuit / main circuit | 2 kV rms / 1 min |
| Rated test voltage open contact | 1 kV rms / 1 min |
| Contact materials | AgNi |
|---|---|
| Mechanical endurance (cycles) | 30 000 000 |
| Minimum load | 10 mA, 5 V |
| Number of contacts | 1 CO |
| Rated current | 6 A |
| Rated load AC-1 | 1500 VA |
| Rated voltage | 250 V AC |
| AC voltage measurement range L-N / L-L | 320 … 400 V |
|---|---|
| Measured parameters | U |
| Monitoring functions | Under, phase failure, phase sequence |
| Number of voltage measurement inputs | 3 (L1 / L2 / L3) |
| Rated AC voltage L-N / L-L | - / 400 V |
| Rated base frequency | 45 … 65 Hz |
| Undervoltage setting range | ≤ 320 V |
| Frequency range | 45 … 65 Hz |
|---|---|
| Nominal voltage | 400 V AC |
| Operating voltage range | 360 … 470 V |
| Power consumption AC / DC | 10 VA / 1.5 W |
| Approvals | UKCA,CE,EAC,cURus |
|---|---|
| Standards | IEC/EN 60947 |
Approvals
3D-models "SSU31/AC400V"