The SSU31 is used to monitor the phase sequence and detect undervoltage and phase failure in three-phase networks.
The monitoring function is used to ensure the drive direction of pumps and conveyor systems, particularly in mobile systems with plug connections. Switching off at a defined undervoltage and phase failure protects against malfunctions and damage due to overheating.

Current type AC (50 Hz)
Nominal voltage 400 V

Housing material PC
Ingress Protection IP 20
Operation temperature -25 … 60 °C
Storage temperature (no ice) -40 … 85 °C
Weight 300 g

Overvoltage category III
Pollution degree 2
Rated test voltage measuring / measuring circuit 2 kV rms / 1 min
Rated test voltage measuring circuit / main circuit 2 kV rms / 1 min
Rated test voltage open contact 1 kV rms / 1 min

Contact materials AgNi
Mechanical endurance (cycles) 30 000 000
Minimum load 10 mA, 5 V
Number of contacts 1 CO
Rated current 6 A
Rated load AC-1 1500 VA
Rated voltage 250 V AC

AC voltage measurement range L-N / L-L 320 … 400 V
Measured parameters U
Monitoring functions Under, phase failure, phase sequence
Number of voltage measurement inputs 3 (L1 / L2 / L3)
Rated AC voltage L-N / L-L - / 400 V
Rated base frequency 45 … 65 Hz
Undervoltage setting range ≤ 320 V

Frequency range 45 … 65 Hz
Nominal voltage 400 V AC
Operating voltage range 360 … 470 V
Power consumption AC / DC 10 VA / 1.5 W

Approvals UKCA,CE,EAC,cURus
Standards IEC/EN 60947
3D-models "SSU31/AC400V"

Current type AC (50 Hz)
Nominal voltage 400 V

Housing material PC
Ingress Protection IP 20
Operation temperature -25 … 60 °C
Storage temperature (no ice) -40 … 85 °C
Weight 300 g

Overvoltage category III
Pollution degree 2
Rated test voltage measuring / measuring circuit 2 kV rms / 1 min
Rated test voltage measuring circuit / main circuit 2 kV rms / 1 min
Rated test voltage open contact 1 kV rms / 1 min

Contact materials AgNi
Mechanical endurance (cycles) 30 000 000
Minimum load 10 mA, 5 V
Number of contacts 1 CO
Rated current 6 A
Rated load AC-1 1500 VA
Rated voltage 250 V AC

AC voltage measurement range L-N / L-L 320 … 400 V
Measured parameters U
Monitoring functions Under, phase failure, phase sequence
Number of voltage measurement inputs 3 (L1 / L2 / L3)
Rated AC voltage L-N / L-L - / 400 V
Rated base frequency 45 … 65 Hz
Undervoltage setting range ≤ 320 V

Frequency range 45 … 65 Hz
Nominal voltage 400 V AC
Operating voltage range 360 … 470 V
Power consumption AC / DC 10 VA / 1.5 W

Approvals UKCA,CE,EAC,cURus
Standards IEC/EN 60947
Approvals
3D-models "SSU31/AC400V"
Skip product gallery

Accessories

S3-M
S3-M
- 10 A @ 250 V
- Module compartment for time or monitoring modules
- Screw terminal

HF-24
HF-24
- Compatible with: SSU31, SSU33L, TSR19

FS-23
FS-23
- Compatible with: SSU31, SSU33L, TSR19

FZ-23
FZ-23
- Compatible with: SSU31, SSU33L, TSR19