505795600
| Housing material | PA 66 |
|---|---|
| Ingress Protection | IP 20 |
| Operation Altitude | Max. 2 000 m |
| Operation temperature | -20 ... 60 °C |
| Relative huminity, no condensation | 95 % |
| Storage temperature (no ice) | -30 ... 80 °C |
| Weight | 20 g (2 pole) / 40 g (4 pole) |
| Pollution degree | 3 |
|---|---|
| Rated impulse withstand voltage | 6 |
| Rated insulation voltage | 690 V |
| Contact materials | AgNi |
|---|---|
| Electrical endurance at rated load AC-1 (cycles) | ≥ 5 x 105 |
| Electrical endurance at rated load DC-13 (cycles) | ≥ 5 x 105 |
| Mechanical endurance (cycles) | ≥ 1 x 107 |
| Rated current AC-1 | 20 A |
| Rated current AC-3 | 6 A, 230 V |
| Rated current DC-3 | 0.15 A, 110 V DC |
| Rated voltage | 690 V |
| Recommended minimum contact load | 50 mA, 17 V |
| Switching frequency at rated load AC-1 (cycles / h) | ≤ 1 200 |
| Switching frequency at rated load DC-3 (cycles / h) | ≤ 1 200 |
| Approvals | UKCA,CE,cULus |
|---|---|
| Standards | IEC/EN 60947 |
| Conductor cross section auxiliary circuit | 2.5 mm2 |
|---|