RMC-AUX11
- NO and/or NC contacts
- Contact material AgNi
- Contact material AgNi
ELDAS®:
505795300
Housing material | PA 66 |
---|---|
Ingress Protection | IP 20 |
Operation Altitude | Max. 2 000 m |
Operation temperature | -20 ... 60 °C |
Relative huminity, no condensation | 95 % |
Storage temperature (no ice) | -30 ... 80 °C |
Weight | 20 g (2 pole) / 40 g (4 pole) |
Pollution degree | 3 |
---|---|
Rated impulse withstand voltage | 6 |
Rated insulation voltage | 690 V |
Contact materials | AgNi |
---|---|
Electrical endurance at rated load AC-1 (cycles) | ≥ 5 x 105 |
Electrical endurance at rated load DC-13 (cycles) | ≥ 5 x 105 |
Mechanical endurance (cycles) | ≥ 1 x 107 |
Rated current AC-1 | 20 A |
Rated current AC-3 | 6 A, 230 V |
Rated current DC-3 | 0.15 A, 110 V DC |
Rated voltage | 690 V |
Recommended minimum contact load | 50 mA, 17 V |
Switching frequency at rated load AC-1 (cycles / h) | ≤ 1 200 |
Switching frequency at rated load DC-3 (cycles / h) | ≤ 1 200 |
Approvals | UKCA,CE,cULus |
---|---|
Standards | IEC/EN 60947 |
Conductor cross section auxiliary circuit | 2.5 mm2 |
---|
Approvals



Documents "RMC-AUX11"