CRINT-R24/DC24V

Pick-up voltage ≤ 0.7 UN
Operating voltage range 0.7 UN … 1.25 UN
Power consumption DC 0.4 W
Release voltage ≥ 0.1 UN

Operation temperature -40...85 °C
Pick-up time ≤ 15 ms
Release time ≤ 8 ms
Storage temperature (no ice) -40...85 °C
Weight 12 g

Insulation resistance at 500 V ≥ 1 GΩ
Test voltage contact / contact 5 kV / 1 min
Test voltage terminal / terminal 1 kV / 1min

Contact materials AgNi + Au
Electrical endurance at rated load AC-1 (cycles) ≥ 50 000
Maximum contact load AC-1 8A / 250 V AC-1
Maximum contact load DC-1 8A / 24 V DC-1
Mechanical endurance (cycles) ≥ 10 000 000
Number of contacts 2 CO
Rated current 8 A
Rated load AC 2 000 VA
Recommended minimum contact load 10 mA / 5 V

Approvals CE,EAC,UKCA,cURus
Standards IEC/EN 61810
Approvals