CMS-10R-DAC/DC12-48V-Z1

- For use in 4G, 3G, 2G mobile networks
- Zone 1: Worldwide
- Inputs: 4 x digital / analogue (0-10 V) switchable, 2 x analogue 4-20 mA (I5 and I6)
- Outputs: 4 x changeover contacts, 10 A @ 250 V AC each
- Contact type: Screw connection
ELDAS®:
CMS-10R-DAC/DC12-48V messaging system
Remote control of outputs and status queries of inputs and outputs via SMS, pager, voice call, push/email notification, remote configuration via web browser (IoT portal), application available for Android/iOS devices, supported communication standards GSM (2G) / UMTS (3G) / LTE (4G), integrated eSIM, operating voltage: 10 ... 48 V DC, Inputs: 6 x digital, Outputs: 4 x changeover contact (10 A / 250 V AC), 50 mm antenna, Power consumption 6 W, Operating temperature range -25 ... 55 °C, IP40, 5 TE DIN, grey plastic housing

Current type DC
Nominal voltage 12 V-48 V

Antenna connector type SMA female
Antenna impedance 50 Ω
Antenna jack torque (max) 1
Antenna return loss > 10 dB
Communication Standards E-GSM (2G), E-UTRA (3G), LTE (4G)
eSIM Embedded
Frequency bands Z1 E-GSM: B2, B3, B5, B8 | E-UTRA: B1, B2, B4, B5, B6, B8, B19 |
LTE-FDD: B1, B2, B3, B4, B5, B7, B8, B12, B13, B18, B19, B20,
B25, B26, B28 | LTE-TDD: B38, B39, B40, B41
Frequency bands Z2 E-GSM: B3, B8 | E-UTRA: B1, B8 | LTE-FDD: B1, B3, B7, B8,
B20, B28A
Network coverage Weltweit

Classification Manual Control (IEC 60730-1)
Operation Type 1 (IEC 60730-1)
Software class Class A (IEC 60730-1)

Housing material PA
Ingress Protection IP 40
Mounting DIN Rail (IEC 60715) and Panel mount
Operation Altitude Max. 2 000 m / 6 562 ft over sea level (without derating)
Operation Position any
Operation temperature -25 … 70 °C / -13 ... 158 °F
Relative huminity, no condensation 10 … 95 %
Storage temperature (no ice) -40 … 85 °C / -40 ... 185 °F
Weight 260 g

Current input impedance 150 Ω
Logic level '0' digital inputs < 4.0 V DC
Logic level '1' digital inputs > 6.0 V DC
Maximal voltage digital inputs 48 V DC
Measurement category 2
Nominal range analogue voltage inputs 4 ... 20 mA, Compliant with IEC 60381-1
Number of analogue current inputs 2
Number of analogue voltage / digital inputs 4
Resolution of analogue inputs 12
Sampling rate per channel 10
Voltage input impedance 196 kΩ

Insulation rating between all ports 2 kV / 1 min
Insulation type Reinforced
Overvoltage category II
Pollution degree 2
Rated impulse voltage 2.5 kV / 1min
Shock/vibration proof IEC 61373

Contact material AgNi
Electrical endurance at rated load AC-1 (cycles) > 30 000
Maximum switching voltage 400 V AC
Number of relay outputs 4
Rated current AC-1 10 A
Rated load AC-1 3
Rated voltage 250 V AC
Recommended minimum load 10 mA / 12 V
Type of terminal CO

Additional power consumption per output 0.45 W
Maximum power consumption 6 W
Nominal operating voltage 10 ... 48 V DC
Nominal voltage 10 ... 48 VDC
Operating voltage range 8.4 ... 60 V DC
Typical power consumption (without any output set) < 1 W

Approvals CE,UKCA
Standards IEC/EN/BSI/UL/CSA 60730,CISPR 32 / EN 55032,IEC 61000-6-2/-3,ETSI EN 301511,ETSI EN 301908-1/-2/-13,IEC 60381-1/-2,IEC/EN/BSI/AS/NZS/SANS 62368

Conductor cross section control / main circuit 4 mm2 / AWG12 (Wire), 2.5 mm2 / AWG14 (Stranded), 1.00 mm2 / AWG17 (Ferrule). Use copper conductors only.
Contact type control / main circuit Screw connection
Dual sleeve control / main circuit 1
Max. wire count control / main circuit 2
Nominal screw torque control / main circuit 0.5 Nm / 4.425 lbf in
Screwdrive control / main circuit PZ2
Stripping Length control / main circuit 8 mm / 0.31"
Approvals
Tools "CMS-10R-DAC/DC12-48V-Z1"

Accessories

CMS-ANT-STUB/INT-50MM
- Antenna for indoor use
- Length 50 mm
- IP65

CMS-ANT-BLADE/INT-150MM
- Device antenna blade 150 mm for indoor use
- Rotatable and tiltable
- without antenna cable

CMS-ANT-MAG1/INT-2.5M
- Antenna with magnetic base
- 2.5m cable length (extendable)

CMS-ANT-MAG2/EXT-2.0M
Magnetic base antenna for outdoor use

CMS-ANT-BRACK/EXT-5M
External antenna for wall or mast mounting

CMS-ANT-SMA
Angled connector SMA, m/f, 90

CMS-ANT-KAB/2.5M
Coaxial cable ComatReleco 2.5 m to CMS-10R

CMS-ANT-KAB/5M
Coaxial cable ComatReleco 5 m to CMS-10R

CMS-ANT-KAB/10M
Coaxial cable ComatReleco 10 m to CMS-10R

CMS-ANT-KAB/20M
Coaxial cable ComatReleco 20 m to CMS-10R

HDR-15-24
15 W DIN rail power supply 24 V

HDR-30-24
30 W DIN rail power supply 24 V

RF01-U2-D
Room temperature sensor with display

WF50 EXT-U4
Outdoor temperature sensor

MV LKM 274
Digital transmitter for PT100/PT1000

PS1
Level probe

NI8-M12-OP6L

Inductive proximity switch