C31L/R AC48V S
| Current type | AC (50 Hz) |
|---|---|
| Nominal voltage | 48 V |
| Operating voltage range | 0.7 UN … 1.25 UN |
|---|---|
| Pick-up voltage | 0.7 UN |
| Power consumption AC / DC | 2.5 VA / 1.2 W |
| Release voltage | > 0.15 x UN / > 0.05 x UN |
| Variant | Railway & LED |
|---|
| Bounce time NO contact AC / DC | 3 ... 6 ms / approx. ≤ 3.5 ms |
|---|---|
| Housing material | PA / PC |
| Maximum switching frequency at rated load | 360 / h |
| Operation temperature | -40 … 70 °C |
| Pick-up time AC / DC | 3 … 10 ms / ≤ 12 ms |
| Release time AC / DC | 2 … 15 ms / ≤ 3.5 ms |
| Storage temperature (no ice) | -40 … 80 °C |
| Weight | 80 g |
| Insulation resistance at 500 V | ≥ 1 GΩ |
|---|---|
| Overvoltage category | III |
| Pollution degree | 3 |
| Test voltage contact / coil | 2 kV / 1 min |
| Test voltage contact / contact | 1.5 kV / 1 min |
| Test voltage open contact | 1.5 kV / 1 min |
| Contact materials | AgCuNi |
|---|---|
| Electrical endurance at rated load AC-1 (cycles) | ≥ 700 000 |
| Inrush current | 40 A, 20 ms |
| Maximum contact load AC | 10 A / 250 V AC-1 |
| Maximum contact load DC | 10 A / 30 V DC-1 |
| Mechanical endurance (cycles) | ≥ 100 000 000 |
| Rated current | 10 A |
| Rated load AC | 2 500 VA |
| Recommended minimum contact load | 50 mA / 10 V |
| Approvals | UKCA,CE,CCC,cURus,EAC,Railway |
|---|---|
| Railway | EN 50155,EN 45545-2 |
| Standards | IEC/EN 61810,IEC/EN 60947 |
Approvals