Skip to main content Skip to search Skip to main navigation

C31D/R DC12V

Current type DC
mA 104 mA
Nominal voltage 12 V
Ohm 115

Operating voltage range 0.7 UN … 1.25 UN
Pick-up voltage 0.7 UN
Power consumption AC / DC 2.5 VA / 1.2 W
Release voltage > 0.15 x UN / > 0.05 x UN

Variant Railway & Free wheeling diode

Bounce time NO contact AC / DC 3 ... 6 ms / approx. ≤ 3.5 ms
Housing material PA / PC
Maximum switching frequency at rated load 360 / h
Operation temperature -40 … 70 °C
Pick-up time AC / DC 3 … 10 ms / ≤ 12 ms
Release time AC / DC 2 … 15 ms / ≤ 3.5 ms
Storage temperature (no ice) -40 … 80 °C
Weight 80 g

Insulation resistance at 500 V ≥ 1 GΩ
Overvoltage category III
Pollution degree 3
Test voltage contact / coil 2 kV / 1 min
Test voltage contact / contact 1.5 kV / 1 min
Test voltage open contact 1.5 kV / 1 min

Contact materials AgCuNi
Electrical endurance at rated load AC-1 (cycles) ≥ 700 000
Inrush current 40 A, 20 ms
Maximum contact load AC 10 A / 250 V AC-1
Maximum contact load DC 10 A / 30 V DC-1
Mechanical endurance (cycles) ≥ 100 000 000
Rated current 10 A
Rated load AC 2 500 VA
Recommended minimum contact load 50 mA / 10 V

Approvals UKCA,CE,CCC,cURus,EAC,Railway
Railway EN 50155,EN 45545-2
Standards IEC/EN 61810,IEC/EN 60947
Approvals
Skip product gallery

Accessories

S3-MR
S3-MR
- 10 A @ 250 V
- Module compartment for pluggable R modules

S3-M0R
S3-M0R
‘- 10 A @ 250 V
- Module compartment for time or monitoring modules

S3-M1R
S3-M1R
‘- 10 A @ 250 V
- Module compartment for time or monitoring modules