C22L/AC48V
- 2 pole
- Changeover contacts, twin contacts
- Contact material AgCuNi
- 6 A @ 250 V AC / 30 V DC
- Changeover contacts, twin contacts
- Contact material AgCuNi
- 6 A @ 250 V AC / 30 V DC
ELDAS®:
Current type | AC (50 Hz) |
---|---|
mA | 55 mA |
Nominal voltage | 48 V |
Ohm | 240 |
Operating voltage range | 0.8 UN … 1.1 UN |
---|---|
Pick-up voltage | ≤ 0.8 UN |
Power consumption AC / DC | 2.5 VA / 1.2 W |
Release voltage AC / DC | > 0.15 x UN / > 0.05 x UN |
Variant | LED |
---|
Bounce time NO contact AC / DC | 3 ... 6 ms / approx. ≤ 3.5 ms |
---|---|
Housing material | PA / PC |
Maximum switching frequency at rated load | 360 / h |
Operation temperature | -40 … 70 °C |
Pick-up time AC / DC | 3 … 10 ms / ≤ 12 ms |
Release time AC / DC | 2 … 15 ms / ≤ 3.5 ms |
Storage temperature (no ice) | -40 … 70 °C |
Weight | 80 g |
Insulation resistance at 500 V | ≥ 1 GΩ |
---|---|
Overvoltage category | III |
Pollution degree | 3 |
Test voltage contact / coil | 2 kV / 1 min |
Test voltage contact / contact | 1.5 kV / 1 min |
Test voltage open contact | 1.5 kV / 1 min |
Contact materials | AgCuNi |
---|---|
Electrical endurance at rated load AC-1 (cycles) | ≥ 1 500 000 |
Inrush current | 15 A, 20 ms |
Maximum contact load AC | 6 A / 250 V AC-1 |
Maximum contact load DC | 6 A / 30 V DC-1 |
Mechanical endurance (cycles) | ≥ 100 000 000 |
Rated current | 6 A |
Rated load AC | 1 500 VA |
Recommended minimum contact load | 10 mA / 5 V |
Approvals | UKCA,CE,EAC,CCC,cURus |
---|---|
Standards | IEC/EN 61810,IEC/EN 60947 |
Approvals





3D-models "C22L/AC48V"