Device installation
– Who will install the CMS-10R?
➔ The CMS-10R may only be installed by qualified electricians.
– Why is no LED lit?
➔ Mount the antenna and connect the device with the appropriate rated voltage (CMS-10R-D: 110 – 240 V AC / CMS-10R-DA and CMS-10R-DAC: 12 – 48V DC).
– What is the status of the LEDs?
➔ Status LEDs Radio signal
These LEDs indicate the currently used radio standard (2G, 3G or 4G).
The colour indicates the signal strength:
LED not lighting up
Operating mode: Fallback: Event storage on the device
Radio network: None
IoT Portal: not connected
LED flashing orange
Operating mode: Fallback: SMS directly to recipient
Radio network: Poor reception
IoT Portal: not connected
LED lighting up orange
Operating mode: Normal operation
Radio networl: Poor reception
IoT Portal: connected
LED flashes green
Operating mode: Fallback: SMS directly to recipient
Radio network: Good reception
IoT Portal: not connected
LED lights up green
Operating mode: Normal operation
Radio network: Good reception
IoT Portal: connected
➔ Status LEDs Outputs
LED not lighting up
Status: Relay switched off. Relay contact is open
Flashing frequency: —
LED lights up
Status: Relay switched off. Relay contact is closed
Flashing frequency: —
➔ RUN LED
LED not lighting up
Status: The device is switched off or is not working
Flashing frequency: —
LED flashing
Status: The device and the firmware are ready for use and are in operation
Flashing frequency: Slow
➔ STAT LED
The LED indicates the operating status.
LED not lighting up
Status: Normal operation
Flashing frequency: —
LED flashing
Status: Firmware update
Flashing frequency: Fast, flashing
LED flashing
Status: Firmware update/restart
Flashing frequency: Slow
LED lights up
Status: Device shuts down/exits all running tasks
Flashing frequency: —
LED flashing
Status: Device shuts down/terminates connection to even IoT platform and mobile network
Flashing frequency: Fast
➔ Status LEDs Inputs
Digital inputs
LED not lighting up
Status: Input value = logic level 0 (low)
Flashing frequency: —
LED lights up
Status: Input value = logic level 1 (high)
Flashing frequency:: —
Analogue inputs
LED not lighting up
Status: Input level ≤ lower threshold value
Flashing frequency: —
LED flashing
Status: Lower threshold value < input level < upper threshold value
Flashing frequency: Slow
LED lights up
Status: Input level ≥ upper threshold value
Flashing frequency: —
– Are the input and output contacts potential-free?
➔ The inputs are not potential-free and must be supplied with the same potential as the device is fed. The outputs are designed as change-over contacts and are potential-free.